Measuring element of UTK displacer level controller is ball float or displacer, measuring element is connected with magnet tube. When level raised, magnet tube moves up and enters external magnetic field. Through magnet induction effect or magnet coupling effect, the magnet controlling switch or offset magnet steel is pulled and makes switch contact on or off. When level goes down, the magnet tube moves down and goes out off the external magnet field. Then the magnetic controlling switch backs to the original state or the offset magnet steel goes down back to new balance position under the action of self-weight, then makes switch contact on or off. In this way, it realizes level controlling and alarming.
 
  • Operating Principle
  • Technical Parameter
  • Model Selection Table
  • Outline and installation
  • Ordering information
◆Nominal pressure: ≤16.0MPa;
◆Measuring accuracy: level controlling: ±4mm;
◆interface controlling: ±6mm;
◆Flange standard: HG/T20592-2009,HG/T20615-2009 or on request
◆Ambient temperature: -40℃~+80℃
◆Operating temperature: -40℃~150℃(high temperature type: 300℃)
◆Medium density: level controller: ρ≥0.5g/cm3
◆interface controller: ρ1 - ρ2≥0.25g/cm3
◆Medium viscosity: ≤ 1St (10-4m2/s)
◆Wetted material: 20, 304, 316L or on request
◆Power supply inlet: G1/2″ (female thread)or on request
◆Explosion-proof: ExdⅡCT4-T6,
◆ExiaⅡCT4-T6
◆Protection class: IP67
◆Relative equipment: safety barrier (see safety barrier recommendation sheet)

 

Contact capacity

Switch type

Max.
voltage AC

Max.
current (A)

Contact point
number

Contact
 resistance
(≯Ω)

Switching speed (≯ms)

Service life
(≮ 104 times)

Reed switch

250

1

SPDT

0.03

3

50

Microswitch

250

5

SPDT

0.03

3

50

 Note: 24V DC is only for intrinsically safe.

◆控制范围:                                                

For level controlling

Model

Measuring
element

Controlling
position

Max.pressure
MPa

Nominal diameter

Alarming setting-point
B (mm)

Range
H (mm)

Remark

UTK100

Ball float

Upper
Or lower limit

6.3

DN40

On request

 

Controlling position non-adjustable

UTK300

Displacer

Upper
Or lower limit

4.0

DN80

On request

 

Controlling
position is adjustable;
The rang of upper limit and
low limit are adjustable.

Upper and lower limits

On request

UTK400

Displacer

Upper
Or lower limit

16.0

DN40

On request

 

Controlling position non-adjustable

For interface controlling

Model

Controlling
position

Max.pressure
MPa

Min.density

Min.density
difference

Alarming setting-point
B (mm)

(g/cm3)

Ball-float

Upper or lower limit

4.0

0.5

0.25

On request

1 UTK-100

Model Code Code meaning
UTK-   Displacer level controller
  100   Flange sealing
  A   Normal type
B   Side-bottom mounted
C   Side-side mounted Ⅰ
D   Side-side mounted Ⅱ
  1   Reed switch
3   Microswitch
  X   Upper limit or low limit
  *   Medium density (g/cm³)
  -    
  *   Alarm setting-point
(distance to upper interface flange mm)
  i Intrinsically safe
d Explosion isolating
UTK-  

Example: UTK-100D3X0.8-178i is flange sealing, side-side mountedⅡtype, microswitch, upper or low limit alarm, medium density is 0.8g/cm³, alarm setting-point is 178mm, intrinsically safe displacer level controller.


2 UTK-300、UTK-400
 
 
Model Code Code meaning
UTK-   Displacer level controller
  300   Top mounted
  400   High pressure type (side-side mounted)
  1   Reed switch
3   Microswitch
  X   Upper or lower limit
  Y   Upper and lower limit (only for UTK300)
  *   Medium density (g/cm³)
  -    
  *   Alarm setting-point
(distance to upper interface flange mm)
  i Intrinsically safe
d Explosion isolating
UTK- -  

Example: UTK-4003X0.8-178i is high pressure type, microswitch, upper or lower limit alarm, medium density is 0.8g/cm³, alarm setting-point is 178mm, intrinsically safe displacer level controller.

 

1.Structure
 

 

2 Safety barrier recommendation sheet

Dandong Top Electronics Instrument Co., Ltd TP5041-EX TP5045-EX
Shanghai Automation Instrument Institute CS8041-EX CS8045-EX
Operating medium
Operating pressure
Operating temperature
Flange standard
Wetted material
Medium density
Alarm setting-point